IBR Ratings
BTU/HR/FT |
|
| |
| Water FLow |
1 G.P.M
500 LBS/HR |
4 G.P.M
2000 LBS/HR |
|
| PRESS,DROPS ENT/EXIT |
98.2* |
582.4* |
PRESS,DROPS Per/Ft |
23.2* |
411.8* |
| 150º F |
370 |
390 |
| 160º F |
440 |
470 |
| 170º F |
500 |
530 |
| 180º F |
570 |
600 |
| 190º F |
640 |
680 |
| 200º F |
700 |
740 |
| 210º F |
770 |
810 |
| 215º F |
800 |
850 |
| 220º F |
830 |
880 |
|
| |
*MILLinches
STEAM Rating 780 BTU/HR/FT (3.25 SQ FT EDR)
Maximum Allowable working Pressure -30 PSI,
Water:15 PSI, Steam.
NOte:
The Pressure Drop MUst be SEPARATELY Calculated FOR each Individual Assembly |
| |
| Water Content 0.3 Gallons Per Linear Foot. |
| |
| Cast Board |
| |
| |
Weight/LB.
Per FT.
APPROX. |
PRICE |
| Cast Iron Base BOard PER LINEAR FT. |
17 |
$41.46 |
|
| |
| Accessories |
| |
| |
Part # |
|
| Valve Enclosures (Inter, Right or Left) |
BVE |
19.48 ea |
| Dummy Covers (4 or 6 Ft.) per foot |
BDC4 |
12.54
|
| 4" End Cap ( RIGHT) |
BECR4 |
7.78
ea |
| 4" End Cap (Left) |
BECl4 |
7.78 ea |
| 6" End Cap ( RIGHT) |
BECR6 |
11.68 ea |
| 6" End Cap (Left) |
BECL6 |
11.68 ea |
| Inside Corner |
BIC |
20.78 ea |
| 6" Flexible Connector |
FLEX6 |
29.9 ea
|
| 9" Flexible Connector |
FLEX9 |
37.7 ea |
| 3/4" Push Nipples |
BPN34 |
1.28 ea |
| 3/4" Vent Plugs |
BVP34 |
1.02 ea |
Tie Bolts with Nuts
|
BTB |
.84 ea |
| Top or Bottom Support |
BTS |
.71 ea |
| CastSlope Assembly Tool |
Bat |
201.5 ea |
|
|
 |
| |
| Assembly and Selection Guide |
|
| |
| Dimensions |
| |
 |
| |
| Assembly Information |
| |
 |
| |
| |
|
NOTE:
For additional Part numbers of other baseboard assemblies refer to master Part # List |
Installation of panels longer than 24” requires push nipples, adhesive and nuts & bolts to be applied wherever section meet. A special assembly tool is available. Installation of panels 6 ft. or longer requires top or bottom support.
Note: I=B=R are determined from tests made is accordance with the I=B=R testing and rating code for baseboard type radiation, including an allowance of 15% for heating effect permitted by the code.
Standard flow rate of 500 lbs. (1gpm) per hour must be used.
Rating Based on active length. Active length same as total length
|
|
|
|